One Phase AC Current Transducer
* Test conditions: auxiliary power supply: +12 VDC, room temperature: 25 ℃.
* Input range: 0~ 1000A;
* Accuracy: class 0.5 (adopts fiducial error);
* Operating temperature: -10~60℃;
* Isolation voltage: 2500 V DC;
* Load capacity: voltage output ≥ 2k Ω, current output ≤ 250 Ω;
* Temperature drift: ≤300ppm/℃;
* Response time: ≤ 300 mS;
* Rated power consumption: <0.5W;
* Output ripple: ≤10mV;
* Frequency range: 45~65Hz (up to 5K, please specify when ordering);
* Surge impact immunity:
Power port one-level ± 0.5KV (L-N/2Ω/integrated wave)
Analog I/O port one-level ±0.5KV (L-N/40Ω/integrated wave);
*Impulse immunity: input / power supply port ± 2KV;
analog I / O port ± 1KV;
* Input overload capacity: 20 times of the measured current nominal value (maximum 500A), applying a repetition of five times a second, interval 300S;
* Storage temperature: -55 ~+65°C; humidity: ≤95% (no dew).