One Phase AC Current Transducer
* Test conditions: auxiliary power supply: +12V, room temperature: 25℃.
* Input range: 0~0.5~ 30A
* Output: 0-5VDC
* Accuracy: class 0.5 (adopts fiducial error)
* Temperature drift: 500 ppm/℃
* Isolation voltage: 2500 V DC
* Load capacity: ≥2 kΩ
* Response time: ≤200 mS
* Rated power consumption: ≤0.4W
* Output ripple: ≤10mV
* Frequency range: 45~65Hz(the highest is 5K, please specify when ordering)
* Surge impact immunity:
Power port one-level ±0.5KV (L-N/2Ω/ integrated wave)
Analog I /O port one-level I/O ±0.5KV (L-N/40Ω/ integrated wave);
* Impulse immunity: Input / power port ±2KV
Analog I /O port±1KV
* Input overload capacity: 20 times and less than 500A, 5 times per second
* Operating condition: Temperature: -10~60℃; Humidity: ≤95%( No dew)
* Storage condition: Temperature: -55~65℃; Humidity: ≤95%( No dew)