One Phase AC Current Transducer
* Input Range: 0~20AAC~300AAC
* Input Frequency: 50Hz~60Hz
* Rated output: 0-5V/0-10V
* Accuracy: 1.0
* Load capability: ≥1MΩ
* Temperature drift: ≤100ppm/℃
* Isolation voltage: ≥2500 V DC
* Response time: ≤200 mS
* Rated power consumption: none
* Output ripple: ≤10mV
* Frequency range: 45~65Hz(up to 5K,please specify when ordering)
* Surge impact immunity:
Power port one-level ± 0.5KV (L-N/2Ω/integrated wave)
Analog I/O port one-level ±0.5KV (L-N/40Ω/integrated wave);
* Impulse immunity: Input / power port ± 2KV
Analog I /O port ± 1KV;
* Input overload capacity: 20 times of the nominal value (maximum 500A)
(Applying a repetition of five times a second, interval 300S)
* Operating condition: 0 ~ 50°C; humidity: ≤95 %( no dew);
* Storage condition: -55 ~+65°C; humidity: ≤95 % (no dew).