One Phase AC Current Transducer

HOME > Current > One Phase AC Current Transducer

*Test conditions: power supply:+24V, room temperature: 25℃.

*Input range: 20A~500A AC(ES3 case style)、0~30A AC(BS2 case style), 0~5A AC(MS1case style)

* Output range: 0-5V/1-5V/0-20mA/4-20mA/0-10V

* Auxiliary power supply: 12VDC, 15VDC, 24VDC, 220VAC  (can be customized)

*Accuracy: class 0.5, class 0.2 

*Load capacity: ≥ 2KΩ (voltage output),   ≤ 250Ω (current output),  ≤500Ω(current output, can be customized)

* Temperature drift:≤200ppm/℃

* Isolation voltage: 2500V DC

* Response time:≤300mS

* Rated power consumption:≤0.4W(≤20mA)

* Output ripple:≤10mV

* Frequency range:45~65Hz (the highest is 5K, please specify when ordering)

* Surge impact immunity: 

  Power port three–level 2000V(L-N/2Ω/ integrated wave)

  Analog I /O port three-level 2000V(L-N/40Ω/ integrated wave)

*Input overload capacity: 20 times of the measured current nominal value(Maximum 500A)(exert one second, repeat five times, interval 300S)

* Operating condition: Temperature:-10~60℃;

                                 Humidity: ≤95%(No dew)

* Storage condition: Temperature: -55~65℃;

                              Humidity: ≤95%(No dew)


Copyright© 2019 SHENZHEN SENSOR ELECTRONIC TECHNOLOGY CO., LTD粤ICP备05079934号-9