One Phase AC Current Transducer
*Test conditions: power supply:+24V, room temperature: 25℃.
*Input range: 20A~500A AC(ES3 case style)、0~30A AC(BS2 case style), 0~5A AC(MS1case style)
* Output range: 0-5V/1-5V/0-20mA/4-20mA/0-10V
* Auxiliary power supply: 12VDC, 15VDC, 24VDC, 220VAC (can be customized)
*Accuracy: class 0.5, class 0.2
*Load capacity: ≥ 2KΩ (voltage output), ≤ 250Ω (current output), ≤500Ω(current output, can be customized)
* Temperature drift:≤200ppm/℃
* Isolation voltage: 2500V DC
* Response time:≤300mS
* Rated power consumption:≤0.4W(≤20mA)
* Output ripple:≤10mV
* Frequency range:45~65Hz (the highest is 5K, please specify when ordering)
* Surge impact immunity:
Power port three–level 2000V(L-N/2Ω/ integrated wave)
Analog I /O port three-level 2000V(L-N/40Ω/ integrated wave)
*Input overload capacity: 20 times of the measured current nominal value(Maximum 500A)(exert one second, repeat five times, interval 300S)
* Operating condition: Temperature:-10~60℃;
Humidity: ≤95%(No dew)
* Storage condition: Temperature: -55~65℃;
Humidity: ≤95%(No dew)