DC Voltage Transducer

HOME > Voltage > DC Voltage Transducer

Test conditions: auxiliary power: +12 V, room temperature: 25°C.
Input range: 0~500VDC;
Output: 0~5VDC, 4~20mA, 0~10VDC, 0~20mA;
Power supply: 12VDC, 15VDC, 24VDC, 220VAC optional;
Accuracy: 0.2;
Load capacity: ≥2KΩ (voltage output), ≤250Ω (current output);
Temperature drift: ≤300ppm/°C;
Isolation voltage: 2500 V DC;
Response time: ≤300 mS;
Rated power consumption: voltage output≤400mW, current output (4~20mA) ≤800mW;
Output ripple: ≤10mV;
Frequency range: (45~65Hz up to 5K, please specify when ordering);
Surge impact immunity:
Power supply port three 2000V (L-N / 2Ω / integrated wave),
Analog I / O port three 2000V (L-N / 40Ω / integrated wave);
Impulse immunity: none;
Input overload capacity: 2 times the rated input value, 1 second 10 times;
Operating temperature: -10 ~ 60°C;
Storage temperature: -40 ~+70°C.