DC Current Transducer
* Test conditions: auxiliary power supply: +12 V, room temperature: 25°C;
* Input range: 0~5A DC;
* Output: 0~5VDC, 4~20mADC, 0~10VDC, 0~20mADC;
* Power supply: 12V/15V/24V DC; 110V/220V AC/DC; (48V power supply can be customized)
* Rated power consumption: <0.8W(+12V) 、<1.5W(+24V);
* Accuracy: class 0.2, class 0.5 (input less than 1mA or greater than 2A is class 0.5);
* Load capacity: load ≥ 2KΩ (voltage Vz output),
load ≤ 250Ω (current Iy, Iz output);
* Temperature drift: ≤300ppm/°C;
* Isolation voltage: 2500 V DC;
* Output ripple: ≤10mV;
* Response time: ≤300 mS;
* Frequency range: none;
* Input overload capacity: 2 times of the rated input value, 1 second 10 times;
* Surge impact immunity:
Power supply port three-level 2000V (L-N / 2Ω / integrated wave),
Analog I / O port three-level 2000V (L-N / 40Ω / integrated wave);
* Impulse immunity: None;
* Storage temperature: -40~70°C;
* Operating temperature: -10~60°C.