Two Phase Current Transducer
* Test conditions: power supply: 24VDC, room temperature: 25℃;
* Input range: 0-0.5~30A AC;
* Output: 0-5V, 1-5V, 0-10V, 0-20mA, 4-20mA DC etc.
* Auxiliary power supply: +12VDC,+15VDC,+24VDC,85-265V AC/DC;
* Accuracy: class 0.5;
* Load capacity: ≥2KΩ(voltage output) ; ≤250Ω(current output);
* Temperature drift: ≤300ppm/℃;
* Isolation voltage: ≥2500 VDC;
* Response time: ≤400 mS;
* Rated power consumption: voltage output=0.5W;current output=1.5W;
* Frequency range: 45Hz-400Hz; ( 1% deviation for 1KHz)
* Surge impact immunity:
Power port three–level ±2KV (L-N/2Ω/ integrated wave)
Analog I /O port three-level ±2KV (L-N/40Ω/integrated wave);
* Impulse immunity: Input / power port ±2KV Analog I /O port±1KV
* Input overload capacity: 20 times of the measured current nominal value(apply one second, repeat 5 times, interval 300S);
* Operating condition: Temperature: -10~60℃; Humidity: ≤95%( No dew)
* Storage condition: -40~+70℃.