3-phase 4-wire AC multi-parameter digital transducer
HOME > Multi-parameter > AC Multi-parameter Digital Transducer

This product is a 3-phase power integrated measurement of 3-phase 3 wire digital isolation transducer. The two- table method is used to measure the full-parameter of three - phase three - wire AC loop. Using high-precision 24-bit dedicated AD chip, the ratio dynamic range can be up to 1000: 1, the measurement parameters are voltage, current, frequency, active power, reactive power, power factor, total accumulative energy and other electrical parameters with high accuracy, good stability and high communication speed. The completely isolated processing technology is with anti-interference ability. Measurement of electrical parameters through the RS-485 digital interface output to achieve long-distance transmission, the product MODBUS protocol is complete compatible with a variety of configuration software or PLC equipment MODBUS (RTU) protocol. It can be applied to power, room monitoring, industrial measurement and other fields.
Data SheetNO, | Item | Date | Unite | Remarks |
1 | Accuracy | 0.2,0.5 | % | 0.2 for voltage and current value only |
Input range | S3 case:500V*30A; S5 case:500V*200A; N1 case:500V*5A; | The maximum range for each specification | ||
Frequency | Frequency response: 20Hz-1KHz; Frequency measurement: 20-600Hz | |||
2 | Baud rate | RS-485(twisted pair line) , RS-232C(treble line, only for N style parts) | bps | Factory default communication format: 9600, N/8/1, address 1; S5 type up to 19.2K; |
Communication | None, Even, Odd, Space | RS422 optional | ||
Parity | 64 | |||
Max. number of nodes | 400W transient voltage | Node | Only for RS-485 | |
Bus protection | RS-485(twisted pair line) , RS-232C(treble line, only for N style parts) | ESD protection and thermosnap | ||
3 | A/D SPEED | 100 | mS | |
4 | Working temperature | -20℃~+60℃ | ||
5 | Isolation voltage | Input/output: 2500V DC for 1 min Input/power supply:2500V for 1 min Output/power supply:2500V for 1 min |
V
| The double isolation part numbers, their output and power supply are grounded together, there is only between the input and output isolation voltage |
6 | Overload | 2 x voltage span 1 sec. 10 for times with interval of 10 sec. 10 x current span for 1 sec. 5 times with an interval of 300 sec (only for hole thru. parts) | The input outside the linear range will result in poor accuracy | |
7 | MTBF | >30000 | Hour | |
8 | Auxiliary power supply | +5V/+12V/+24V/+48V/ AC220V | V | 220VAC,DC only for N case parts |
9 | Power consumption | ≤250mW(+12V),≤500mW(+24V) | mW | Power consumption depends on power supply to be used |
10 | Temperature drift | ≤300 | ppm/℃ | (-20℃~+60℃) |
CE-AJ4*-**BS3 Case Type
CE-AJ4*-**BS3 Installation dimension
CE-AJ4*-**MN1 Case Type(220V AC)
CE-AJ4*-**MN1 Installation Diagram
CE-AJ4*-**DS5 Case Type
CE-AJ4*-**DS5 Installation Digram
Terminal definition and connection diagrams
(Note: All 3-phase 4-wire system (three tables) product’s voltage input are not required to connect to the zero line, the other wiring is as same as the following figure)
Three-phase four-wire double isolation S3-type product wiring refers to Figure 6.1.
The terminal 7can provide voltage +5 V (the maximum current is 20mA.)for RS485 / RC232C converter.
Wiring diagram of 3-phaes 4-wire CE-AJ41-**BS3
Wiring diagram of 3-phaes 4-wire CE-AJ42-**BS3 (Vss is the ground of RS485 output)
Three-phase four-wire N1-type product wiring
The terminal 3 can provide voltage +5 V (the maximum current is 20mA.)for RS485 / RC232C converter.
Wiring diagram of 3-phase 4-wire CE-AJ42-**MN1
Wiring diagram of 3-phase 4-wire CE-AJ42-**MN1
Wiring diagram of 3-phase 3-wire S5-type products (current punch input, Φ11mm, maximum 100A)
Wiring diagram of 3-phase 4-wire CE-AJ42-**DS5 products
² Available with wide power supply: DC: 10-30V or 10-55V
² With odd parity, even parity, no parity, 2 stop bits and other communication methods are free to set.
² Communication speed optional, the maximum communication speed to 115200 bps.
² The intelligent transducer with the smallest size and wide current measurement range in the peer
² Electroplating has a positive and negative accumulation, and power-down storage function.
² With red and green light-emitting diode instructions function, the red light indicates the normal operation of the product (100mS flashing), the green light indicates the product communication.
² High anti-interference ability, the input, output and power port to resist the surge voltage up to 2KV or more.