Intelligent monitoring terminal for arrester working condition

HOME > PRODUCT > New Product

  • ​ENTRIES:Part Number GuideData SheetFAQ
  • Lightning damage is one of the main factors affecting the safety of power grid operation. Due to the low insulation level of the distribution network system and generally no lightning protection wire, lightning strikes are particularly prominent. At present, as the main means of lightning protection in distribution networks, lightning arresters are widely used in distribution lines and distribution transformers. In areas where lightning activities are relatively frequent, the failure rate of arresters has remained high. Faced with the large quantity and wide distribution of arresters, it brings huge manpower and economic pressure for power outage maintenance and troubleshooting. For this reason, our company has specially developed a lightning arrester working condition Internet of Things monitoring system.

    This monitoring unit has passive wireless (no external power supply, wireless transmission), low power consumption, GPS positioning, comprehensive lightning current parameter monitoring: peak value, effective value, wave head, duration, energy, frequency and other related parameters. Through the synchronous detection of time, environmental parameters, and electrical parameters of the arrester, the use of big data and neural network algorithms to effectively eliminate the impact of environmental factors such as pollution, temperature, humidity, and interphase capacitance, coupled with multiple international and industry standards such as Qrs, impact times, leakage current and other international and industry standards, it can effectively predict and judge the working conditions of the arrester, and realize the pre-judgment repair and accurate fault alarm in management.


    Data Sheet

    Product function


    1

    Full parameters

    Real-time monitoring of leakage   current, lightning times, time, peak value, effective value, wave head,   duration, energy, frequency and other parameters.

    2

    Self-powered

    Product integrates solar panel + lithium battery

    3

    Self-monitoring

    Monitor the internal battery power, solar charging current, and   self-power consumption of the product.

    4

    Remote setting

    The lightning   current alarm threshold and leakage current alarm threshold can be set   remotely.

    5

    Remote upgrade

    The firmware of   the acquisition unit can be upgraded remotely

    6

    Synchronization   detection

    With synchronous   monitoring function of time, temperature and humidity

    7

    Fault location

    With GPS   positioning function, accurately determine the location of the fault

    Main Specifications

    1

    Measurement error

    10%

    2

    Input signal

    Lightning current: 300A20kA Leakage current: 100mA

    3

    Power supply

    6V 1.5W solar,battery 2000maH

    4

    Output signal         

    NB-IOT+GPS

    5

    Linear range

    0120%

    6

    Number of acquisition channels

    One way lightning current, one way leakage current

    7

    Power consumption

    Send 200mA, standby 4mA

    8

    Protocol

    MODBUS protocol

    9

    Operating temperature

    -20℃~+60 

    10

    Working humidity

    Not more than 95% (temperature 30, no dew)

    11

    Dimensions

    See Figure 1 for details

    12

    Shell material

    metallic material

    13

    Support frequency   band

    Band1/2/3/5/8/12/13/17/18/19/20/25/26/28/66/70   (currently only the Band5 frequency band is open for the product)

    14

    Bandwidth

    100bps100Kbps

    15

    Transmit power

    23dBm±2dB

    16

    Acceptance   sensitivity

    -139dBm±1dB

    17

    Network protocol

    COAP protocol

    18

    Platform

    Telecom AEP   platform

    19

    Synchronization   detection

    It has the   function of synchronous monitoring of time, temperature and humidity.

    20

    Remote setting

    The lightning   current alarm threshold and leakage current alarm threshold can be remotely   set through the SSET cloud platform

    21

    Remote upgrade

    The firmware of   the acquisition unit can be upgraded through the telecom AEP platform



    CE-AL12-5THT2-1.0


    Appearance and Dimensions:

    blob.png

    Installation instructions

    blob.png

    Features

    l  Lightning monitoring: detection of all parameters of lightning current: real-time monitoring of parameters such as number, time, peak value, effective value, wave head, duration, energy, frequency and so on.

    l  Condition monitoring: According to the international and industry standard Qrs, the number of impacts, leakage current and other multi-parameter criteria, effective prediction and judgment of the operating conditions of the arrester.    

    l  A variety of probes: it is convenient for the direct installation of various aperture arresters, and the lightning monitoring needs of different nodes (flexible, open).

    l  Accurate judgment: effectively eliminate the influence of temperature, humidity, and pollution on the leakage current, and monitor the status of the arrester in real time.

    l  Environmental monitoring: It has the synchronous monitoring function of time, temperature and humidity.

    l  Fault location: with GPS positioning function, accurately determine the location of the fault.

    l  Intelligent duplex: remote software update; can remotely set the threshold value, early warning value, alarm value, communication times and other parameters in each unit.

    l  Easy to install: self-monitoring of the environment before installation to ensure the use of the product, just screw the bottom of the arrester, light and handy.

    l  Passive wireless: no need for power supply, with power warning, charging monitoring, and multiple wireless communication methods such as NB, 4G, and LORA.

    l  Accurate counting: It has the functions of preventing repeated counting of multiple thunders and identifying the impact of power grid fluctuations.