Single Phase AC Current Transducer
This device is a AC current isolation transducer, input and output are not common-grounded, input signal is AC current, output signal is 0-5V. With characteristics of high precision, high voltage isolation, low temperature drift, small size, easy installation , comply with international standards. Can widely used in telecommunications, electricity, railways, industrial control and other fields.
Data Sheet* Test conditions: auxiliary power supply: +12V, room temperature: 25℃.
* Input range: 0~0.5~ 30A
* Output: 0-5VDC
* Accuracy: class 0.5 (adopts fiducial error)
* Temperature drift: 500 ppm/℃
* Isolation voltage: 2500 V DC
* Load capacity: ≥2 kΩ
* Response time: ≤200 mS
* Rated power consumption: ≤0.4W
* Output ripple: ≤10mV
* Frequency range: 45~65Hz(the highest is 5K, please specify when ordering)
* Surge impact immunity:
Power port one-level ±0.5KV (L-N/2Ω/ integrated wave)
Analog I /O port one-level I/O ±0.5KV (L-N/40Ω/ integrated wave);
* Impulse immunity: Input / power port ±2KV
Analog I /O port±1KV
* Input overload capacity: 20 times and less than 500A, 5 times per second
* Operating condition: Temperature: -10~60℃; Humidity: ≤95%( No dew)
* Storage condition: Temperature: -55~65℃; Humidity: ≤95%( No dew)
BH1 case style
H1 case style installation dimensions
Pin 3: VCC, positive terminal of auxiliary power supply.
Pin 4: GND, negative terminal of auxiliary power supply.
Pin 5: OUT, voltage output.
Pin type installation method,convenient to install on the PCB board,secure and reliable.
Small size, convenient for centralized installation, can save space.
High precision, low temperature drift,high reliability.