One Phase AC Current Transducer
* Test conditions: room temperature: 25℃;
* Input Range: 0~300A AC;
* Input current threshold value: 230mAAC;
* Accuracy: 1.0 (adopts fiducial error);
* Response time: ≤ 150 mS;
* Contact capacity: DC30V, 1A;
* Conduction characteristics: <0.6Ω;
* Rated power consumption: none;
* Output ripple: none;
* Frequency range: 45~65Hz(up to 5K,please specify when ordering);
* Surge impact immunity:
Power port one-level ± 0.5KV (L-N/2Ω/integrated wave),
Analog I/O port one-level ±0.5KV (L-N/40Ω/integrated wave);
* Impulse immunity: Input / power port ± 2KV,
Analog I /O port ±1KV;
* Operating temperature range: -10 ℃ ~ 50 ℃ 20% -90% RH;
* Input overload capacity: 20 times of the nominal value of measured current(maximum 500A)
(Apply a second repeat 5 times, interval 300S);
* Operating temperature: -10 ~ 60°C; humidity: ≤95 %( no dew);
* Storage temperature: -55 ~+65°C; humidity: ≤95 % (no dew).