One Phase AC Current Transducer
* Test conditions: auxiliary power: +24 VDC, room temperature: 25 ℃.
* Input range: 0~20AAC~500AAC
* Output: voltage, current, switch, frequency, tracking
* Power supply: 12VDC, 15VDC, 24VDC
* Accuracy: 0.5class
* Load capacity: load ≥ 2KΩ (voltage output Vz), load ≤ 250Ω (current output Iy, Iz)
* Temperature drift: ≤400ppm/℃
* Isolation voltage: ≥2500 V DC
* Response time: ≤300 mS
* Quiescent Current: ≤10mA
* Rated power consumption: ≤0.4W, ≤0.5W
* Output ripple: ≤10mV
* Frequency range: 45~65Hz (up to 5K, please specify when ordering);
* Surge impact immunity:
Power port three-level ± 2KV (L-N/2Ω/integrated wave)
Analog I/O port three-level ±2KV (L-N/40Ω/integrated wave);
* Input overload capacity: 20 times the nominal value of the measurement current (maximum 500A)
(Applying a repetition of five times a second, interval 300S);
* Operating temperature: -10~ 60°C; humidity: ≤95% (no dew);
* Storage temperature: -55 ~+65°C; humidity: ≤95% (no dew).