DC Voltage Transducer

HOME > Voltage > DC Voltage Transducer

Input range: 0~5000VDC;
Output: 0~20mA, 4~20mA, 10V, ±10V, 5V,  ±5V;
Power supply: +12~24V DC;
Accuracy: 0.2;       
Load capacity: ≥2KΩ (voltage output); ≤250Ω (current output);
Temperature drift: ≤100ppm/℃;
Isolation voltage:
Between the input signal and the output signal, isolation voltage 10KVDC, leakage less than 1mA, duration of 60 seconds;
Between the input signal and the auxiliary power supply, isolation voltage 10KVDC, leakage less than 1mA, duration of 60 seconds;
Between the output signal and the auxiliary power supply, isolation pressure 6KVDC, leakage less than 1mA, duration of 60 seconds;
Response time: ≤300 uS;
Rated power consumption: <2.5W;
Output ripple: ≤10mV;
Surge impact immunity:
Input port: four 6000V (L-N / 2Ω / integrated wave),
Power port: four 4000V (L-N / 2Ω / integrated wave);
Analog I / O port: three 2000V (L-N / 40Ω / integrated wave),
Input overload capacity: the maximum input voltage of 8KV, applied to repeat 10 times a second, interval 10S;
Operating temperature: -20~70℃; Humidity: ≤ 90% (no dew);
Storage temperature: -40 ~+70°C.