One input one output DC current signal isolator

HOME > Current > Standard Signal Isolator

  • ​ENTRIES:Part Number GuideData SheetFAQ
  • The main function of the signal isolator is to isolated transmit the input DC voltage (current) signal into the standard current or voltage signal. The product contains an efficient micro power isolated power supply that provides an isolated power supply to the pre-stage primary sensor while powering the internal signal processing circuitry. The products are widely used in analog signal isolation conversion of industrial field, such as communications, power rail, industrial control and other automation and control fields.


    Data Sheet

    Test conditions: auxiliary power: +24 V, room temperature: 25 ℃;
    Input range:
    Voltage range 75mV~300V DC,
    Current range 10mA~5A DC;
    Output: 0-20mA, 4-20mA, 0-5V, 0-10V, 0-15V(special)
    Note: When input signal is 1-5V or 4-20mA, it is not allowed to output a negative signal.
    Please specify the requirements of "shielding negative signal" when ordering, as described in section IX.1.
    Power supply: +24VDC(-15%~+20%)
    Power distribution output: 24VDC±3.6V/25mADC
    Accuracy: 0.2;        
    Load capacity: current output ≤500Ω; voltage output ≥2kΩ;
    Temperature drift: ≤200ppm/℃;
    Isolation voltage: 2500VDC;  
    Response time: ≤100 mS;                 
    Rated power consumption: <1.1W;
    Output ripple: ≤10mV;
    Frequency response range: none;
    Surge immunity:
    Power port three ±2KV(L-N/2Ω/ integrated wave),  
    Output port three±2KV (L-N/40Ω/ integrated wave);
    Impulse immunity:
    input/power port ± 2KV, analog I/O port ± 1KV;  
    Input overload capacity:
    2 times nominal value for the measured voltage(apply a second, repeat 10 times, interval 10S);
    20 times nominal value for the measured current apply a second, repeat 5 times, interval 300S);
    Operating temperature: -20~70℃, humidity: ≤95%(no dew);
    Storage temperature: -40~+70℃.

    112.png

    MD4-黑.jpg


    MD4  case

    D2.JPG

                                                                                       DIN35 rail-mounted or screw-mounted installation


    113.png

    Treble isolated structure:
    Input, output and auxiliary power supply are isolated from each other;
    Using electromagnetic isolation technology, stable and reliable performance;
    The output port and power port can withstand 2KV surge impact;
    Product accuracy is better than 0.2;
    Provides the isolated 24V distribution power output, facilitates a sensor power supply;
    The use of 18mm shell guide rail installation, space utilization is high;
    Wiring plug terminals, easy wiring and maintenance.

    Related Products