Standard Signal Isolator

HOME > Current > Standard Signal Isolator

Test conditions: auxiliary power: +24 V, room temperature: 25 ℃;
Input range:
Voltage range 75mV~300V DC,
Current range 10mA~5A DC;
Output: 0-20mA, 4-20mA, 0-5V, 0-10V, 0-15V(special)
Note: When input signal is 1-5V or 4-20mA, it is not allowed to output a negative signal.
Please specify the requirements of "shielding negative signal" when ordering, as described in section IX.1.
Power supply: +24VDC(-15%~+20%)
Power distribution output: 24VDC±3.6V/25mADC
Accuracy: 0.2;        
Load capacity: current output ≤500Ω; voltage output ≥2kΩ;
Temperature drift: ≤200ppm/℃;
Isolation voltage: 2500VDC;  
Response time: ≤100 mS;                 
Rated power consumption: <1.1W;
Output ripple: ≤10mV;
Frequency response range: none;
Surge immunity:
Power port three ±2KV(L-N/2Ω/ integrated wave),  
Output port three±2KV (L-N/40Ω/ integrated wave);
Impulse immunity:
input/power port ± 2KV, analog I/O port ± 1KV;  
Input overload capacity:
2 times nominal value for the measured voltage(apply a second, repeat 10 times, interval 10S);
20 times nominal value for the measured current apply a second, repeat 5 times, interval 300S);
Operating temperature: -20~70℃, humidity: ≤95%(no dew);
Storage temperature: -40~+70℃.