Standard Signal Isolator
Test conditions: room temperature: 25℃;
Input range: 4-20mADC;
Pressure drop: <3V@20mADC (2V);
Output: 4-20mADC;
Auxiliary power: passive;
Accuracy: 0.2;
Load capacity: ≤300Ω;
Temperature drift: ≤50ppm/℃;
Isolation voltage: 2500V DC;
Response time: ≤20mS;
Rated power consumption: none;
Output ripple: none;
Frequency response range: none;
Input overload capacity: Current: ≤50mA;
Surge immunity:
Input / output port: three 2KV (L-N / 40Ω / integrated wave);
Impulse immunity: none;
Operating temperature: 20~70℃; humidity: ≤95%((no dew);
Storage temperature: -40~+70℃.