3-phase 3-wire AC multi-parameter digital transducer

HOME > Multi-parameter > Transducers with Both Analog output and Digital Interface

  • ​ENTRIES:Part Number GuideData SheetFAQ
  • This product is an intelligent isolation transducer of electrical integrated measurement and transmission. It can measure the full-parameter of three-phase three-wire AC loop. Using high-precision 24-bit dedicated AD chip, the ratio dynamic range can be up to 5000: 1, the measurement parameters are voltage, current, frequency, active power, reactive power, power factor, total accumulative energy and other electrical parameters with high accuracy, good stability and high communication speed. The completely isolated processing technology is with anti-interference ability. Measurement of electrical parameters through the RS-485 digital interface output to achieve long-distance transmission, the product MODBUS protocol is complete compatible with a variety of configuration software or PLC equipment MODBUS (RTU) protocol. It can be applied to power, room monitoring, industrial measurement and other fields

    Data Sheet

    NO.

    Item

    Name   of items

    Date

    Unite

    Remarks

    1

    Accuracy

    Accuracy

    0.5

    %


    Temperature drift

    <300

    ppm/   

    -20~70

    2


    Input range

    Voltage:AC:0~500V, currentAC:0~200A;



    3


    Operating   temperature

    -20~70


    4

    Digital output

    Baud rate

    4800,9600(default),19200,38400,57600,115200

    bps


    Parity

    None, Even, Odd


    The   default data format: N, 8,1

    Communication   distance

    1200(RS-485)

    m

    RS485   repeater can extend the communication distance

    Max.   number of nodes

    64

    Node


    Bus   protection

    400W transient   voltage


    ESD protection and thermosnap

    A/D   SPEED

    200

    ms


    5

    Analog output

    Output  

    Output   a 1-way voltage and current signal 0-5V/0-20mA or 1-5V/4-20mA or 2.5±2.5V/10±10mA or 3±2V/12±8mA are free to choose



    Output   ripple

    <10

    mV


    Overload capacity

    Voltage output ≥ 500Ω, current   output ≤ 300Ω (24V DC power supply can be 800Ω)

    Ω


    Response   time

    <200

    ms


    6

    Power source

    Power   supply

    DC:11~28V; AC/DC:85~265V;

    V

    Wide   power supply

    Power consumption

    <1W(24V);

    W

    Different   Auxiliary power, different power consumption

    7

    Reliability

    MTBF

    >30000

    hour


    Isolation voltage

    Input/output:   2500V DC for 1 min

    Input/power supply: 2500V for 1 min

    Output/power supply: 2500V for 1 min

    V

    The double   isolation part numbers, their output and power supply are grounded together, there is only   between the input and output isolation voltage

    Overload

    2 x voltage span 1   sec. 10 for times with interval of 10 sec.

    10 x current span for 1 sec. 5 times with an interval of 300 sec (only   for hole thru. parts)


    The input outside   the linear range will result in poor accuracy

    Electromagnetic   Compatibility

    Anti-lightning   surge: input ± 4KV; power supply side, digital port, analog output port: ±   2KV;

    Anti-group   pulse: ± 2KV input; power supply side, digital port, analog output port: ±   2KV




    blob.png

    DS5-2.jpg

    CE-AJ31-3**DS5 Case Type

      31.jpg

    Installation Diagram


    blob.png

    CE-AJ31-3**DS5 3-phase 3-wire wiring diagram


    ²  Available with wide power supply: DC: 11-28V, AC/DC: 85-265V.

    ²   Digital and analog output at the same time, digital is communication output and analog output is programmable.

    ²  The analog output can be freely programmed to set the positive and negative power measurement or the inductive and capacitive     polarity measurement of the power factor.

    ²  Analog output can be a 1-way current and a 1-way voltage signal at the same time, eight output functions of 0-5V/0-20mA or 1-     5V /4-20mA or 2.5±2.5V/10±10mA or 3±2V /12±8mA, can be set freely.

    ²  Communication output can be freely set the communication rate and parity, the maximum communication speed is up to 115200     bps.

    ²  With the open-phase, voltage and current phase sequence error detection function. To provide voltage , current vector and the          RMS output.

    ²  High anti-interference ability, the input, output and power port to resist the surge voltage up to 2KV or more.