Multi-channel DC Multi-parameter Digital Transducer

HOME > Multi-parameter > DC Multi-parameter Digital Transducer

  • ​ENTRIES:Part Number GuideData SheetFAQ
  • The main function of this product is to centralized measurement convert multi-channel standard DC transmission signal into digital signal output, can measure 8 channels of current and 4 channels of voltage input signals. Multi - channel DC intelligent transmitter can be widely used in a variety of industrial control and measurement systems, and mainly measure the 4 ~ 20mA or 0 ~ 10V output signal of a variety of pressure, temperature, flow and power transducer. Output communication interface is RS485 or RS232, wide range of power supply DC 9 ~ 30V, using the standard MODBUS-RTU communication protocol.

    Data Sheet

    Input signal

    Input: 8 channels of 0-20mA current and 4 channels of  0-10V voltage.

    Overload: overload 1.2 times the range can be measured correctly, overload 2 times the range of input 1S is not damaged;

    Current Channel: the input impedance is 110Ω;

    Voltage Channel: the input impedance is > 100KΩ;

    Data update cycle: 800mS;

    Communication output

    Output interface: RS-485 (twisted pair line) ±15KV ESD protection, or RS-232 interface ±2KV ESD protection;

    Communication protocol: standard MODBUS-RTU protocol;

    Baud rate: 1200, 2400, 4800, 9600(default), 19200 bps; 

    Parity: Odd parity, even parity, no parity (default), set by software;

    Address: 01H to FFH, factory default 01, set by software;

    Isolation: voltage and current input are isolated from power supply and communication, the isolation voltage is 2500V DC;

    Accuracy: 0.5;

    Power supply: DC 9~30V ;

    Power consumption: <0.5W;

    Operating temperature: -20℃~60℃; 

    Storage temperature: -40℃~85℃, relative humidity: 5% to 95% no dew;

    Installation: standard DIN rail installation of 35mm

    Volume: 122mm * 70mm * 43mm;

    Weight: 130 gram.


    blob.png

      MN3.jpg

    CE-AD81-34MN3 case style


    N3.jpg

    CE-AD81-34MN3 DIN rail mounting dimensions

    blob.png

                                                                                              Terminal definitions table

    Using 24-bit dedicated AD chip, high-accuracy measuring, can reach class 0.2.

    The wide ratio dynamic range, greater than 1000: 1.

    Use plug terminal wiring, easy for site.  

    Available with wide power supply: DC: 10-30V.

    High reliability, power port to resist the surge voltage up to 4KV.