3-phase 4-wire AC multi-parameter digital transducer

HOME > Multi-parameter > AC Multi-parameter Digital Transducer

  • ​ENTRIES:Part Number GuideData SheetFAQ
  • This product is a 3-phase power integrated measurement of 3-phase 3 wire digital isolation transducer. The two- table method is used to measure the full-parameter of three - phase three - wire AC loop. Using high-precision 24-bit dedicated AD chip, the ratio dynamic range can be up to 1000: 1, the measurement parameters are voltage, current, frequency, active power, reactive power, power factor, total accumulative energy and other electrical parameters with high accuracy, good stability and high communication speed. The completely isolated processing technology is with anti-interference ability. Measurement of electrical parameters through the RS-485 digital interface output to achieve long-distance transmission, the product MODBUS protocol is complete compatible with a variety of configuration software or PLC equipment MODBUS (RTU) protocol. It can be applied to power, room monitoring, industrial measurement and other fields.

    Data Sheet

    NO,

    Item

    Date

    Unite

    Remarks

    1

    Accuracy

    0.2,0.5

    %

    0.2 for voltage and current value only

    Input range

    S3 case:500V*30A;  

    S5 case:500V*200A; N1 case:500V*5A;


    The maximum range for each specification

    Frequency

    Frequency response: 20Hz-1KHz; Frequency   measurement: 20-600Hz



    2

    Baud rate

    RS-485(twisted pair line) , RS-232C(treble   line, only for N style parts)

    bps

    Factory default communication format:   9600, N/8/1, address 1; S5 type up to 19.2K;

    Communication

    None, Even, Odd, Space


    RS422 optional

    Parity

    64



    Max. number of nodes

    400W transient voltage

    Node

    Only for RS-485

    Bus protection

    RS-485(twisted pair line) , RS-232C(treble   line, only for N style parts)


    ESD protection and thermosnap

    3

    A/D SPEED

    100

    mS


    4

    Working temperature

    -20~+60



    5

    Isolation voltage

    Input/output:   2500V DC for 1 min

    Input/power supply2500V   for 1 min

    Output/power supply2500V   for 1 min

     

    V

     

    The double isolation part numbers, their   output and power supply are grounded together, there is only between the input and output   isolation voltage

    6

    Overload

    2 x voltage span 1   sec. 10 for times with interval of 10 sec.

    10 x current span   for 1 sec. 5 times with an interval of 300 sec (only for hole thru.   parts) 


    The input outside the linear range will   result in poor accuracy

    7

    MTBF

    >30000

    Hour


    8

    Auxiliary power supply

    +5V/+12V/+24V/+48V/ AC220V

    V

    220VAC,DC only for N case parts

    9

    Power consumption

    250mW(+12V),≤500mW(+24V)

    mW

    Power consumption depends on power supply   to be used

    10

    Temperature drift

    300

    ppm/

     (-20~+60)


    blob.png

    231.jpg

    CE-AJ4*-**BS3 Case Type

    16.png

    CE-AJ4*-**BS3 Installation dimension

    232.png

    CE-AJ4*-**MN1 Case Type(220V AC)

    17.png

    CE-AJ4*-**MN1 Installation Diagram

    211.png

    CE-AJ4*-**DS5 Case Type


    18.jpg

    CE-AJ4*-**DS5 Installation Digram

    Terminal definition and connection diagrams


    (Note: All 3-phase 4-wire system (three tables) product’s voltage input are not required to connect to the zero line, the other wiring is as same as the following figure)

    Three-phase four-wire double isolation S3-type product wiring refers to Figure 6.1.

    The terminal 7can provide voltage +5 V (the maximum current is 20mA.)for RS485 / RC232C converter.


    图片36.png


    Wiring diagram of  3-phaes 4-wire CE-AJ41-**BS3


    图片37.png

     Wiring diagram of 3-phaes 4-wire CE-AJ42-**BS3 (Vss is the ground of RS485 output)

     

     

    Three-phase four-wire N1-type product wiring 

    The terminal 3 can provide voltage +5 V (the maximum current is 20mA.)for RS485 / RC232C converter.

    233.png


    234.png  

     

    Wiring diagram of 3-phase 4-wire CE-AJ42-**MN1 

    Wiring diagram of 3-phase 4-wire CE-AJ42-**MN1

          Wiring diagram of 3-phase 3-wire S5-type products (current punch input, Φ11mm, maximum 100A)


    235.png

    Wiring diagram of 3-phase 4-wire CE-AJ42-**DS5 products

    ²  Available with wide power supply: DC: 10-30V or 10-55V

    ²  With odd parity, even parity, no parity, 2 stop bits and other communication methods are free to set.

    ²  Communication speed optional, the maximum communication speed to 115200 bps.

    ²  The intelligent transducer with the smallest size and wide current measurement range in the peer

    ²  Electroplating has a positive and negative accumulation, and power-down storage function.

    ²  With red and green light-emitting diode instructions function, the red light indicates the normal operation of the product (100mS       flashing), the green light indicates the product communication.

    ²   High anti-interference ability, the input, output and power port to resist the surge voltage up to 2KV or more.


    Related Products