Three phase four wire true RMS AC voltage transducer
This device is a 3-phase AC voltage isolation transducer. It is applied the principle of electromagnetic isolation and true RMS measurement. After True-RMS conversion, it can measure three-phase AC voltage non-sinusoidal alternating signal RMS, isolated and linearly output standard voltage or current signal. The product is widely used in non-standard waveform distortion sine wave real-time signal detection and monitoring.
Test conditions: auxiliary power: 220VAC, room temperature: 25°C;
Input Range: 0~600VAC;
Output: 0~5VDC, 0~10VDC, 0~20mADC, 4~20mADC;
Power supply: 85~265VAC/DC;
Accuracy: 0.5;
Load capacity: ≥2KΩ (voltage output), ≤250Ω (current output);
Temperature drift: ≤350ppm/°C;
Isolation voltage: ≥2500 VDC;
Response time:≤350 mS;
Rated power consumption: 1W (voltage output); 2W (current output);
Output ripple: ≤10mV;
Frequency range: (45~65Hz up to 5K, please specify when ordering);
Surge immunity:
Power port level ± 0.5KV (L-N/2Ω/integrated wave)
Analog I / O port.± 0.5KV (L-N/40Ω/ integrated wave)
Impulse immunity: input / power port ± 2KV, analog I / O port ± 1KV;
Input overload capacity: Voltage: 2 times the nominal value;
Operating temperature: -10 ~ 60°C; humidity: ≤95 %( no dew);
Storage temperature: -55 ~+65°C; humidity: ≤95 % (no dew).
MSK csae
SK outline installation dimensions
Wiring diagram
Each phase voltage is true RMS measurement;
High precision, low temperature drift;
Can rail and screw installation, easy on-site installation;
High reliability, can be more than 2KV surge.