Three Phase Self Power High AC Current Transducer
This device is a self power 3-element high AC current isolation transducer. Adopts the principle of electromagnetic isolation, can sample the high AC current, and isolated output 0 ~ 10V standard signal. The inputs and outputs are electrically isolated from each other, completely linear relationship between the input signals and the output signals. Can be widely used in motor current real-time detection/monitoring, and motor starts over current protection system. Wide application in the coal mining machine, excavators and other large mechanical electrical current testing.
Data Sheet* Input range: 0~3000A(Long-term input current 1500A);
* Output range: 0-10V;
* Accuracy: class 0.5;
* Load capacity: load ≥ 2KΩ;
* Temperature drift: ≤50ppm/℃
* Isolation voltage: AC 6000V (50Hz). Leakage less than 1mA, lasts for 60 seconds;
* Response time: 40 mS ~300mS (Response time increases as input range decreases)
* Rated power consumption: none
* Output ripple: ≤10mV;
* Frequency range: 45~65Hz(up to 5K, please specify when ordering);
* Surge impact immunity:
Power port one-level ± 0.5KV (L-N/2Ω/integrated wave)
Analog I/O port one-level ±0.5KV (L-N/40Ω/integrated wave);
* Impulse immunity: input / power port ± 2KV, analog I /O port ± 1KV;
* Input overload capacity: 20 times of the measurement current nominal value of the measurement current (maximum 500A) (Applying a repetition of five times a second, interval 300S);
* Operating temperature: -20~ 75°C; humidity: ≤95% (no dew);
* Storage temperature: -55 ~+65°C; humidity: ≤95% (no dew).
* Installation: screw installation.
RW6 style product outline drawing
Installation dimensions
Connection diagram
* High impact current, detecting of the instantaneous current is up to 3000A, can be used for motor starting current detection and motor short-circuit current protection.
* Adopts the electromagnetic isolation technology, stable performance, low temperature drift.
* The terminal uses the compression spring method, no need the screw knob, the lead wire installation is simple and convenient.
* High precision, accuracy is superior to class 0.5.