Three Phase AC Current Transducer
* Power supply: 12VDC, 15VDC, 24VDC, 220VAC (optional);
* Input range: 0~80AAC;
* Output: 0~5V ,0~20mA,4~20mA, 0~10V(optional);
* Accuracy: class 0.5;
* Load capacity: voltage output ≥ 1KΩ, current output ≤ 300Ω;
* Temperature drift: <300ppm/℃;
* Isolation voltage: DC 2500V;
* Response time: ≤300 mS;
* Rated power consumption: ≤1W, ≤2W
* Output ripple: ≤10mV
* Frequency range: 45~65Hz (up to 5K, please specify when ordering)
* Surge impact Immunity:
Power port one-level ± 0.5KV (L-N / 2Ω / integrated)
Analog I / O port one-level ± 0.5KV (L-N / 40Ω / integrated wave);
* Impulse immunity: Input / power port ± 2KV, Analog I / O port ± 1KV
* Input overload capacity: 20 times of the measured current nominal value (maximum 500A), (apply one second repeat 5 times, interval 300S).
* Operating temperature: -20℃~+70℃;
* Storage temperature: -55 ~+65°C; humidity: ≤95% (no dew).
* Installation: rail or screw installation.