Three Phase AC Current Transducer

HOME > Current > Three Phase AC Current Transducer

* Test conditions: room temperature: 25℃;

* Input range: 0~1AAC~30AAC  ;

* Output: voltage, current, frequency, tracking;

* Power supply: 12VDC, 15VDC, 24VDC;

* Accuracy: class 0.2;

* Load capacity: load ≥ 2KΩ (voltage output), load ≤250Ω (current output);

* Temperature drift: ≤500ppm/℃;

* Isolation voltage: ≥2500 V DC;

* Response time: ≤300 mS;

* Rated power consumption: voltage output is 0.5W; current output is 2 W

* Output ripple: none;

* Frequency range: 45~65Hz(up to 5K, please specify when ordering);

* Surge impact immunity: 

   Power port one-level ± 0.5KV (L-N/2Ω/integrated wave) 

   Analog I/O port one-level ±0.5KV (L-N/40Ω/integrated wave);

* Impulse immunity: Input / power port ± 2KV ; Analog I /O port ± 1KV;

* Input overload capacity: 20 times of the measured current nominal value of  (maximum 500A),   (apply one second repeat 5 times, interval 300S).;

* Operating temperature: -10~ 60°C; humidity: ≤95% (no dew);

* Storage temperature: -55 ~+65°C; humidity: ≤95% (no dew).


Copyright© 2019 SHENZHEN SENSOR ELECTRONIC TECHNOLOGY CO., LTD粤ICP备05079934号-9