Single phase split core AC current digital transducer

HOME > Current > One phase AC transducer with digital interface

  • ​ENTRIES:Part Number GuideData SheetFAQ
  • This product is a split core single-channel current measurement digital isolation transducer. It can measure the current of the AC circuit. Using high-precision 24-bit dedicated AD chip, the ratio dynamic range can be up to 1000: 1. True RMS measurement of current is with high accuracy, good stability and high communication speed, the completely isolated processing technology is with anti-interference ability. Measurement of electrical parameters through the RS-485 digital interface output to achieve long-distance transmission, the product MODBUS protocol is complete compatible with a variety of configuration software or PLC equipment MODBUS (RTU) protocol. It can be applied to power, room monitoring, industrial measurement and other fields.


    Data Sheet

    NO.

    Item

    Date

    Unite

    Remarks

    1

    Accuracy

    0.5, 1.0

    %

    Current 20A or less, 1.0

    Input range

    500A


    The maximum range for each specification

    Frequency

    Frequency response: 20Hz-1KHz;



    2

    Baud rate

    115.2K, 57.6K, 38.4K, 19.2K, 9600(default)   4800, 2400, 1200

    bps

    Factory default communication format:   9600, N / 8/1, address 1; S5 type up to 19.2K;

    Communication

    RS-485(twisted pair line) , RS-232C(treble   line, only for N style parts)


    RS422 optional

    Parity

    None



    Max. number of nodes

    64

    Node

    Only for RS-485

    Bus protection

    400W transient voltage


    ESD protection and thermosnap

    3

    A/D SPEED

    100

    mS


    4

    Working temperature

    -20~+60



    5

    Isolation voltage

    Input/output:   2500V DC for 1 min

    Input/power supply2500V   for 1 min

    Output/power supply2500V   for 1 min

     

    V

     

    The double isolation part numbers, their   output and power supply are grounded together , there is only between the input and output   isolation voltage

    6

    Overload

    2 x voltage span 1   sec. 10 for times with interval of 10 sec.

    10 x current span   for 1 sec. 5 times with an interval of 300 sec (only for hole thru.   parts) 


    The input outside the linear range will   result in poor accuracy

    7

    MTBF

    >30000

    hour


    8

    Auxiliary power supply

    +5V/+12V/+24V/+48V/ AC220V

    V

    220VAC,DC only for N case parts

    9

    Power consumption

    ≤250mW(+12V)≤500mW(+24V)

    mW

    Power consumption depends on power supply   to be used

    10

    Temperature drift

    ≤300

    ppm/

     (-20~+60)


    33.png

    Case Style (marked in the figure Unit: mm)


     CE-AI12-**GS4 product outline

    34.png

          Installation diagram of CE-AI12-**GS4

    35.png

                                                                                                                Wiring drawing of  CE-AI12-**GS4

    Available with wide power supply: DC: 10-30V or 10-55V
    On-site installation is easy, opening and closing installation, convenient and quick.
    Can be bipolar measurement, with positive and negative active power and cumulative energy measurement function.
    The intelligent transducer with the smallest size and wide current measurement range in the peer.
    Energy has positive and negative cumulative function, with power-down storage.
    With red and green light-emitting diode instructions function, the red light indicates the normal operation of the product (100mS flashing), the green light indicates the product communication.
    High anti-interference ability, the input, output and power port to resist the surge voltage up to 2KV or more.