1. Overview
The device is a standard signal isolator with a 24V DC power output.
It works on high-linearity analog optocoupler principle. The device
converts 4-20mA dc current into 4-20mA dc current or 0-5v(or 1-5V)
dc voltage with single output or double outputs. Meanwhile, it supplies
an isolated 24V DC power to the input section. The input, outputs
and power supply are electrically isolated from each other. The
unit features in their high accuracy, high isolation, low drift
and wide range of operation temperature. They can well avoid the
common-mode noise and power line interference generated during the
transmission of signals from transducers or instruments. It is especially
suitable to use in these devices, which requires electrically isolated,
such as transducers and meters. It may be widely used in measuring
and controlling systems with PLC, Computer and automatic control
systems.
2. Part numbers

3. Specifications
Input:
4-20mA dc
Equivalent
input impedance: about 250W
Overload:
2 times of full span (1 second, 10 times)
Power
output: 24V±3V, 25mA
Output:
4-20mA dc and 0-5V dc(or 1-5V dc)
Load capability:
Current output: £300W,
Voltage output: 5mA
Accuracy:
Single output: 0.2%, Double output: 0.5%
Temperature
drift: Single output: 150ppm/°C, Double output: 250ppm/°C
Response
time: £200mS
Isolation
voltage: 2500V DC/1 minute
Power
consumption: Single output: £1.5W,
Double output: £2W
Operating
temperature: 0-50°C
Power
supply: +24V±10%
Case style:
S3
4. Connections

Single output:
Terminal 1: IN+, Positive input
Terminal 2: 0V, Ground of power output
Terminal 3: +E, Positive power output
Terminal 5: VCC, Positive power supply
Terminal 6: GND, Negative power supply
Terminal 8: OUT-, Negative output
Terminal 9: OUT+, Positive output |
Double output:
Terminal 1: IN+, Positive input
Terminal 2: 0V, Ground of power output
Terminal 3: +E, Positive power output
Terminal 4: GND, Negative power supply
Terminal 5: VCC, Positive power supply
Terminal 6: OUT2-, Negative output 2
Terminal 7: OUT2+, Positive output 2
Terminal 8: OUT1-, Negative output 1
Terminal 9: OUT1+, Positive output 1 |
Don't use all terminals named NC. Don't connect terminal 2 for
2-wire transducer.
5. Case style and Mounting diagram(mm)
S3 case style is shown in Fig. 3. Dimensions: L x W x H: 36 x 83
x 76 mm. Type 35 DIN rail mounting or screw mounting shown in Fig.4.
The spacing between terminals is 5.08 mm.

6. Notes
1. Please check the part numbers, number of products according to
the packing list and labels on the products carefully before use.
2. Please make sure to connect input, output and power supply correctly
in accordance with the connection diagram of your part number before
power on.
3. Conductive dust and corroding gases may damage the circuit and
connections. They are hazardous to the product. Don't operate in
that environment.
4. Please ensure the terminal screws are tightened securely and
reliably before measuring with probes of meters directly on the
terminals.
5. If more than one standard signal isolators are mounted together,
keep a space more than 10 mm between adjacent units.
6. The standard signal isolator has been calibrated before delivery.
Please contact the company if readjustment is required.
7. Don't disassemble the standard signal isolator. Please avoid
impact or falling down from a high place. Do not remove or damage
the labels on the product.
8. Please take additional and reasonable means for lightning protection,
especially when the input and output wires of the standard signal
isolator are exposed outdoor. |