| Product: 1 Element DC Hall Effect
Analog Current Transducer
Series: CE-IZ04-E Case Style E
Input Range: 10mA-10A ~30-1200A
Output: 0-5V / 4-20mA
Power Source:±12
V /±15V
Accuracy: 1.0%
1. List of Options
| SERIES |
OUTPUT |
POWER SOURCE |
WINDOW(mm) |
CASE STYLE |
INPUT RANGE |
| CE-IZ04-E |
9:0-4V,3:0-5V |
5:±12V
6:±15V
|
20.5*10.5 |
E1 |
0-50~600A |
| 2:0-50mA |
12.7*7 |
E3 |
0-50A |
| 12.7*7 |
E3 |
100A |
| 9:0-4V,3:0-5V
4:0-20mA,
5:4-20mA
|
F21 |
E4 |
10mA~10A |
| F21 |
E4 |
0-50~400A |
| F43 |
E5 |
10mA~10A |
| F60 |
E6 |
0-300~1200A |
| 9:0-4V,3:0-5V |
PCB |
LX |
0-5~50A |
2 .Specifications
| LINEARITY RANGE |
1.5 TIMES OF NOMINAL
CURRENT |
| OVERLOAD CAPABILITY |
20 times of the maximum
of measuring range |
2
times of the maximum of measuring range |
| ACCURACY |
1% |
0.5% |
1% |
| OFFSET VOLTAGE |
±20mV |
|
±40mV |
| OFFSET CURRENT |
|
±0.2mA |
|
| HYSTERESIS ERROR |
±10mV |
±0.2mA |
±20mV |
| TEMPERATURE DRIFT |
£250ppm/°C |
200ppm |
500ppm |
| RESPONSE TIME |
£10us |
£1us |
£3us |
| CURRENT CONSUMPTION |
£25mA |
£10ma+
output current |
£25mA |
| ISOLATION |
3KVRMS/50Hz/min |
| OPERATING TEMPERATURE RANGE |
-10°C~+80°C |
| STORAGE TEMPERATURE RANGE |
-25°C~85°C |
| FIRE RETARDANCY |
UL94-V0 |
3. Connection:
The current carrying cable must pass through the window. The
phase of output is the same as that of the current passing
the window in the direction of the arrow indicated on the
case.
Wiring of Terminals for case style E1, E4, E5, E6,E7:
1. +15V/+12V Power Source
2. -15V/-12V Power Source
3. Output
4. Ground
Wiring of Terminals for case style E3 :
+:+15V/+12V Power Source
-:-15V/-12V Power Source
M:Output
4.Cases of series E
Type E1:

Type E3:

Type E4:

Type E5:
Type E6:

Type E7:
NOTE: Case Style E4,5(10mA-10A)are mainly used for
monitoring system for current leakage.
Application Characteristic: Can be used for measuring
DC, AC, pulsed currents, etc. The output of the transducer
reflects the real wave of the current carrying conductor.
Characteristic of Products: Small size, light in weight,
less power consumption, window structure, electrically isolating
the output of the transducer from the current carrying conductor,
no insertion loss.
Application: Frequency conversion timing equipment,
various POWER SOURCE, UPS, electric welding machine, transformer
substation, numerical control machine tool, electrolyzing
equipment, electroplating equipment, electric powered locomotive,
microcomputer monitoring, electric power net monitoring.
Notes:
1. Connect the terminals of POWER SOURCE, outputs respectively
and correctly, never make wrong connection.
2. Two potentiometers can be adjusted, only if necessary,
by turning slowly to the required accuracy with a small screwdriver.
3. The best accuracy can be achieved when the window is fully
filled with bus-bar (current carrying conductor).
4. The in-phase output can be obtained when the direction
of current of current carrying conductor is the same as the
direction of arrow marked on the transducer. |