| Product: 1 Element DC Hall Effect
Analog Current Transducer
Series: CE-IZ04-C Case Style C
Input Range: 100A~10000A
Output: 0-5V / 4-20mA
Power Source:±12 V / ±15V
Accuracy: 1.0%
1. List of Options
| SERIES |
OUTPUT |
POWER SOURCE |
WINDOW(mm) |
CASE STYLE |
INPUT RANGE |
| CE-IZ04-C |
9:0-4V,3:0-5V |
5:±12V
6:±15V
|
F42 |
C1 |
0-200~2000A |
| 9:0-4V
3:0-5V
4:0-20mA
5:4-20mA
|
62*15 |
C2 |
0-300~1000A |
| 85*15 |
C3 |
0-300~2500A |
| 125*26 |
C4 |
0-800~6000A |
| 150*40 |
C5 |
0-800~6000A |
| 9:0-4V
3:0-5V
|
F22 |
C8 |
50~500A |
| F35 |
C9 |
100~800A |
| 9:0-4V
3:0-5V |
104*20 |
C10 |
0-600~2500A |
0-4V
0-5V |
182*70 |
C11 |
0-4000~10000A |
41*11 |
C12 |
0-200~800A |
| 9:
0-4V
3: 0-5V
4: 0-20mA
5: 4-20mA
|
85x27
|
C13 |
0-600~2500A |
2.Specifications
| LINEARITY RANGE |
1.5 times of the maximum of measuring range |
RESPONSE TIME |
10uS |
| OVERLOAD CAPABILITY |
20 times of the maximum of measuring range |
CURRENT CONSUMPTION |
£25mA |
| ACCURACY |
1% |
ISOLATION |
3KVRMS/50Hz/min |
| OFFSET VOLTAGE |
±20mV |
OPERATING TEMPERATURE RANGE |
-10°C~+80°C |
| HYSTERESIS ERROR |
±10mV |
STORAGE TEMPERATURE RANGE |
-25°C~85°C |
| TEMPERATURE DRIFT |
£500ppm/°C |
FIRE RETARDANCY |
UL94-V0 |
3. Connection: The current carrying cable must pass
through the window. The phase of output is the same as that
of the current passing the window in the direction of the
arrow indicated on the case.
Wiring of Terminals for case style C1, C2, C3, C4, C5, C8,
C9, C12:
1. +15V/+12V Power Supply
2. -15V/-12V Power Supply
3. Output
4. Ground
Wiring of Terminals for case style C10:
1. +12V Power Supply
2. Ground
3. +Output
4. -Output
Wiring of Terminals for case style C11:
1. +15V/+12V Power Supply
2. Output
3. Ground
4. -15V/-12V Power Supply
Wiring of Terminals for case style C13:
1. +15V/+12V Power Supply
2. Ground
3. -15V/-12V Power Supply
4. Ground
5. Output
4. Cases of series C
Type C1:

Type C2:

Type C3:

Type C4:

Type C5:

Type C8:

Type C9:

Type C10:

Type C11:

Type C12:

Type C13:
Application Characteristic: Can be used for measuring
DC, AC, pulsed currents, etc. The output of the transducer
reflects the real wave of the current carrying conductor.
Characteristic of Products: Small size, light in weight,
less power consumption, window structure, electrically isolating
the output of the transducer from the current carrying conductor,
no insertion loss.
Application: Frequency conversion timing equipment,
various POWER SOURCE, UPS, electric welding machine, transformer
substation, numerical control machine tool, electrolyzing
equipment, electroplating equipment, electric powered locomotive,
microcomputer monitoring, electric power net monitoring.
Notes:
1. Connect the terminals of POWER SOURCE, outputs respectively
and correctly, never make wrong connection.
2. Two potentiometers can be adjusted, only if necessary,
by turning slowly to the required accuracy with a small screwdriver.
3. The best accuracy can be achieved when the window is fully
filled with bus-bar (current carrying conductor).
4. The in-phase output can be obtained when the direction
of current of current carrying conductor is the same as the
direction of arrow marked on the transducer. |