1 Please check the number, part number and specifications
of the products with packing list and label before use.
2 Please connect input, output and power source correctly according
to corresponding connection diagram and check carefully before powered.
3 Requirement of power source:
Accuracy: 2% (min.) Ripple: Vpp£0.4%
4 It is not allowed that the part numbers with current output
operate when their outputs is open or with load resistance more than
250W. For the part numbers with voltage
output they are not allowed to operate when their outputs is closed
or with load resistance less than 2KW.
5 Conductive dust and gases corroding metal may damage the isolation.
They are hazardous to the product. Don't operate in that environment.
6 You should screw the terminals tightly before you measure the
output signal on the output terminals with the probes of instrument,
7 If you need test the accuracy of the product, you have to use
an instrument with higher accuracy than that of the product at least
15 minutes later after power on the product.
8 If the product operates in environment with strong electrical
noise, please shield the input wires and sensing window, meanwhile
let the output wire as shorter as possible. When many products are
mounted together, please mount the products on a rail with width of
35mm and keep the interval at least 10mm between products. Use M3
screw to mount the product on plane.
9 The zero adjusting and accuracy of all delivered products were
adjusted and calibrated. Don't readjust. Please contact us In case
you need adjusting.
10 Don't alter or tear up any labels on product.
|
|