| Home >Product>
CE-IJ31 |
|
CE-VJ03,CE-VJ03A |
|
| PRODUCT: |
1 Element AC Analog Voltage Transducer |
| SERIES: |
CE-VJ03 |
|
CE-VJ03A(TRUE RMS) |
| INPUT RANGE: |
1V~1000V |
| OUTPUT: |
5V or 4-20 mA |
| ACCURACY: |
0.2% or 0.5% |
| RESPONSE TIME: |
£300ms |
| POWER SOURCE: |
+12V or +15V or +24V |
| LOAD CAPABILITY: |
Voltage Output³2kW |
|
|
Current Output£250W |
| QUISCENT POWER CONSUMPTION: |
=250mW |
Specifications:
Other
Typical Specifications
| Item |
Test condition |
Index |
| Class 0.2 |
Class 0.5 |
Thermal Drift |
+12V, 25°C |
£200ppm/°C |
£500ppm/°C |
| Output Ripple |
+12V, 25°C |
10mV |
15mV |
| Output Load |
+12V, 25°C
Vz (3) output
|
³2kW |
+12V, 25°C
Iz (4) and Iy (5) output
|
£250W |
| Operating Temperature |
+12V |
0~50°C |
| Isolation Withstanding
Voltage |
1 min. |
£2500vdc |
| 1 min. |
£1500
Vac RMS |
|
| |
| Series |
Operating Principle |
Isolation Voltage |
Response Time
Range 0 to 90% FS |
Overload Capacity |
Quiescent Power (mW) |
Mounting |
| Vz,Vd,Vg
,Iz Output |
Iy Output |
CE-VJ03
CE-VJ03A |
Electro-
magnetic
|
£2500VDC |
£300ms |
2 Times10/sec |
50(H)
180(S) |
250 |
PCB Surface or Din rail |
List of options: Remark
| Series |
Output |
Power Source |
Window Opening
(mm) |
Case Style |
Accuracy |
Input Range( RMS ) |
| CE-VJ03 |
3: 0~5V DC (Vz)
|
2: 12V
|
M:none |
H1**** |
0.5 |
10V,50V
100V, 110V, 220V, 250V, 380V, 400V, 500V, 1000V |
| CE-VJ03A |
1: 0~5V RMS(Vg)*
3: 0~5V DC (Vz)
4: 0~20mA (Iz)
5: 4~20mA (Iy)**
7: 4~20 mA (Id)***
8: 0~10V DC (Vd)* |
2: 12V
3: 15V
4: 24V
5: ±12V
6
: ±15V |
S2
S3 |
0.2
0.5 |
8: 110V
9: 220V |
S3 |
* Output types(Vg,Vy,Vd) and accuracy 0.2 are not available in series CE-IJ03A ;
** Loop resistance from 0 to 250W ,Contact factory for loop resistance above 250W ;
*** Select 24V Power supply for output of 4-20mA Id;
**** This case style needs an extra voltage divider .
Part Number Example: CE-VJ03-52MS2-0.2/0~250V
Description: 1element AC Voltage Transducer, Input: 0~250V, Output:
4~20mA, Power source: +12V, no Window (terminal input), Accuracy:
0.2%, Case Style: S2.
Diagrams: (Click one of
small diagrams to magnify it in the right rectangle)
| Case Style |
Installation |
Connection |
| |
|
|
| |
|
|
| |
|
|
|
 |
Application for CE-VJ03:
- Monitor for over/under voltage
- Power monitoring
- Multi-point instrumentation needs
- Sense phase loss
Application for CE-VJ03A
- Chopped waveform drivers
- Phase fired controlled devices
- Quickly varying voltage supplies
- Harmonic voltages
Notice:
- Selection of output signal: Please select power source >12V
at 0~10V output.
- The H1 type must be used with corresponding current limiting
resistance. The current limiting resistance should not be out
near by the output terminal (larger voltage drop).
- The output signal and the power source must be earthed in common.
Please keep right connection, don't in error set.
|