| Company
Profile |
| Certificate |
Current Transducer |
Voltage Transducer |
Power Transducer |
Frequency Transducer |
Multi-parameter Transducer |
Other |
|
Select Guide for Transducer with Analog Output |
|
Select Guide for Transducer with Digital Output |
|
Select Guide for Transducer with LED Display |
|
Select Guide for Hall Effect Sensor |
| Software Download |
| Connection of RS-485/232 Converter |
| System Connecting For Transducer with Digital Output |
Application and Programming for Transducer with Digital Output |
Transducer with Analog Output |
Transducer with Digital Output |
Transducer with LED Display |
Hall Effect Sensor |
Vehicle Detector |
| Notices to Users |
| Notices for Installation |
| FAQ For Transducer with RS485 Digital Output |
| FAQ for Transducer with Analog Output |
| Product Knowledge |
| AC 1-element |
| AC 2-element |
| AC 3-element |
| DC |
| AC 1-phase |
| AC 3-phase 3-wire |
| AC 3-phase 4-wire |
| DC |
| AC 1-element |
| AC 3-phase 3-wire |
| AC 3-phase 4-wire |
| AC 1-element |
| AC 3-phase 3-wire |
| AC 3-phase 4-wire |
| AC 3-phase 4-wire, multi-cross |
| Power Factor Transducer |
| Standard Signal Isolator |
| Resistance Transducer |
| Potentiometer Transducer |
| Switch Values Data Logger |
| Ethernet Converter |
| Power Source |
| Vehicle Detector |
| Current Transducer |
| Voltage Transducer |
| Power Transducer |
| Frequency Transducer |
| Other |
| Multi-parameter Transducer |
| Current Transducer |
| Voltage Transducer |
| Multifuction Transducer |
| Current Transducer |
| Voltage Transducer |
| Case A Transducer |
| Case B Transducer |
| Case C Transducer |
| Case D Transducer |
| Case E Transducer |
| Case F Transducer |
| Case LX Transducer |
0-55Hz~5KHz |
|
|
| Instructions of Switching Value Data Logger with 8 Inputs |
Home >> Quick Search >> Other >> Switch Values |
|
|
1. Part numbers
- CE-AK10-3 —— 8 switching value inputs, RS-485 output interface, MODBUS protocol, no isolation, S case style.
2. Specifications
- Input —— Passive contacts (Dry contacts).
- Withstand voltage of the passive contacts —— ≥24VDC
- Output data —— Values of 8 channels of switching signal input. (“1” means “on”, “0” means “off”.)
- Output interface ——RS-485 bus. 1200m, ±15KV ESD protection.
- Baudrate —— 1200, 2400, 4800, 9600, 19.2k bps.
- Refreshing period —— 100 mS.
- Quiescent power consumption —— <350 mW (+24V).
- Power supply —— +24V
- Operating temperature —— 0℃~+50℃.
- Storage temperature —— -20℃~+80℃ (RH:5%~95% no condensing).
3. Case style and dimentions
- S case style (as the photo shown below). Dimensions: 83×36×29.5 (L x W x H) mm

|
4. Connections: Pin 1~8: Eight inputs. Com: the common input.

|
| |
5. Protocol : It is supposed that the all following ID address is 01 and the baudrate code is 06(9600bps).
5.1 The command “To read the data of all switching value inputs”:
A: The Message from the master equipment: |
Address of the slave equipment |
Function code |
Address of the first register |
Quantity of Registers |
CRC-L |
CRC-H |
| 0x01 |
0x03 |
0x00 |
0x00 |
0x00 |
0x01 |
0x84 |
0x0A |
|
Note: The values data will be stored in the first register 0000H, the high order byte is before the low order byte. |
B: The correct responded message from the slave equipment (the data logger): |
Address of the slave equipment |
Function code |
Byte count |
Data |
CRC-L |
CRC-H |
| 0x01 |
0x03 |
0x02 |
0x00 |
Values data |
Check code |
Check code |
|
Note: “Values data” mean 8 bits of switching values. The most significant bit is the datum of switching value input 8 and LSB is the datum of switching value input 1. |
| |
5.2 The command “To modify the address and baudrate”:
A: The Message from the master equipment:
(Change the address from 01 to 02; set new baudrate to 9600 bps <code 06>) |
| Address of the slave equipment |
Function code |
Address of the first register |
Quantity of Registers |
Data bytes count |
Data |
CRC-L |
CRCH |
| 0x01 |
0x10 |
0x00 |
0x20 |
0x00 |
0x01 |
0x02 |
0x00 |
Values data |
Check code |
Check code |
|
Note: The data of new address and baudrate will be stored in the first register 0020H, the high order byte is address data and the low order byte is baudrate code. Codes for baudrate setting: 03-1200bps, 04-2400bps, 05-4800bps, 06-9600bps, 07--19200bps. |
| B: The correct responded message from the slave equipment (the data logger): |
| Address of the slave equipment |
Function code |
Address of the first register |
Quantity of Registers |
CRC-L |
CRCH |
| 0x01 |
0x10 |
0x00 |
0x20 |
0x00 |
0x01 |
0x00 |
0x03 |
|
| |
| |
|
|