Split Core AC Current Transducer
Specifications:
Series |
Operating Principle |
Isolation Voltage |
Response Time |
Overload Capacity |
Power Consumption (mW) |
Mounting |
| Vz,Vd,Vg,Iz,output |
Iy Output |
CE-IJ03-xxGS4
CE-IJ03A-xxGS4
|
Electro-magnetic induction |
2500VDC |
≤250mS |
20 times or <5/ sec at 500A |
360 |
450 |
Din rail/Screw |
2. Part numbers:
Series |
Output |
Power Supply |
Window(mm) |
Case Style |
Accuracy |
Rated Input |
|
3:0-5VDC(Vz)
4:0-20mA(Iz)*
5:4-20mA(Iy)*
8:0-10VDC(Vd)** |
2:12V
3:15V
4:24V
0:Self Power
|
G:ф31 |
S4 |
1.0 |
5A,10A,15A,25A,
30A,50A,75A,100A,
120A,150A,200A,250A,300A |
* For output Iz and Iy,load would be less than 250Ω ,Contact us for above 250Ω <RL ≤500Ω.
**Output Id not available in CE-IJ03A.
Part Number Example: CE-IJ03-32GS4-1.0/50A
Description:
Spilt core single-phase AC current transducer,Output:0-5V, power supply:+12V,,Aperture: ф31mm,Case style:S4,Accuracy:1.0,Input current:0-50A.
Connections Diagram :

Case Style Dimensions :

Application:
1、Directly connect to PLC
2、Sense motor stalls and short circuits
3、Industrial instrumentation
4、Process control loops
Notice:
1
、If you want to open/ close the split core,press and move the orange bolt to the open/close direction.
2、The
conductor carrying the input current should pass through the center of the aperture as perpendicularly as possible. And lock the bolt.
3、Make sure the polarities are in right connetion, The output and the power supply must be common grouded.
3、If there is a meter is used to test thd output of the transducer,please make sure the accuracy of the meter is higher than the transducer. |